Leonard Valve Megatron 10NB-LF Bi-metal Complete Water Temperature Control Station

Call for pricing & availability: 1-833-251-4591

Write a Review
Availability:
Usually Ships in 7 to 10 Days
Manufacturer Part Number:
Megatron 10NB-LF
Inlet:
4"
Outlet:
4"
WARNING: Cancer and Reproductive Harm - www.p65warnings.ca.gov

Leonard Valve Megatron 10NB-LF Bi-metal Complete Water Temperature Control Station.

LEONARD MEGATRON® MODEL 10NB-LF Complete Water Temperature Control Station to include:

• 4” bottom inlet connections (copper tube)

• 4” top outlet connection (copper tube)

• Large thermostatic water mixing valves with DURA-trol solid bimetal thermostat (with Extended 7 Year Limited Warranty) directly linked to hot and cold valve porting, adjustable high temperature limit stop set for 120F (49C)*, color-coded dial: C-H, locking temperature regulator, inlet union angle strainer checkstops

• Full port ball valve, pressure gauge on mixed water outlet piping

• Small thermostatic water mixing valves with DURA-trol solid bimetal thermostat (with Extended 7 Year Limited Warranty) directly linked to hot and cold valve porting, adjustable high temperature limit stop set for 120F (49C)*, color-coded dial: Cold-Hot, integral checkstops on inlets.

• Full port ball valve on outlet of small mixing valve

• Dial thermometer (range:0 to 140F, -10 to 60C) on mixed water outlet of the system.

• Outlet Test Connection with ball valve and 1¼” connection.

• Full port ball valve mounted downstream of test connection on mixed water outlet of the system

• Inlet piping manifold with full port ball valves and dial thermometers (20 to 240F, -7 to 116C on hot supply, 0 to 140F, -10 to 60C on cold supply) on hot and cold supply inlets

• Subassembly with return piping, 2”, with aquastat, circulator, dial thermometer (0 to 140F, -10 to 60C), balancing valve (with positive shutoff) to balance system, and check valve

• Aquastat with temperature differential of 5 to 30F (3 to 17C)

• GFCI* switch. The GFCI switch will be used to turn the circulator on or off for setup. *Ground Fault Interrupter

• Bypass piping, 2”, with check valve and isolation ball valve to connect to 2” method # 5 piping

• Maximum operating pressure: 125 PSIG (860KPA)

• System mounted on 2 separate struts, galvanized. Struts shall be assembled with three hole flat angle plate on corners, four hole tee plates or two hole flat plate connectors on all other support pieces using 3/8” grip lock nuts and 3/8”x 1” hex head cap screws, washers and lock washers.

• All electrical connections to be completed by Electrical Contractor

• Standard pump is B&G PL-55B

Quality Plumbing Supply is a proud distributor of Leonard Valve products. This Leonard Valve Megatron 10NB-LF Bi-metal Complete Water Temperature Control Station is a direct replacement manufactured by Leonard Valve.  Order this Leonard Valve Megatron 10NB-LF today! Usually ships in 7-10 business days. Some products may incur additional freight charges.