Manufacturer Part Number:
Megatron XL-690-LF
Model/Series:
Megatron
Inlet:
1"
Outlet:
1 1/4"
Return:
3/4"
WARNING: Cancer and Reproductive Harm - www.p65warnings.ca.gov

Leonard Valve Megatron XL-690-LF Wax Lead free Complete Water Temperature Control Station

 

 High Low Thermostatic Water Mixing Valve with 0.5 GPM (1.9) l/min) minimum flow capacity, 1.0 GPM (3.8 l/min) to ASSE 1069

 1” inlets, 1-1/4” outlet (25mm x 32 mm)

 Integral combination check-stops with strainers and wall support

 125 PSI (8.6 BAR) maximum operating pressure.

 Copper encapsulated thermostatic element assemblies with Teflon coated shuttle

 Temperature adjustment range, 90-140ºF (32-60ºC) **

 Internal parts of stainless steel  Rough bronze finish

 Full port ball valve mounted downstream of test connection on mixed water outlet of the system

 Inlet piping with full port ball valves and dial thermometers (20 to 240°F, -7 to 116°C on hot supply, 0 to 140°F,-10 to 60°C on cold supply) on hot and cold supply inlets

 Return piping, ¾”, with aquastat, circulator (TACO 0013), dial thermometer (0 to 140°F, -10 to 60°C), balancing valve (with positive shutoff) to balance system, and check valve.

 Bypass piping, ¾” with check valve and isolation ball valve to cold inlet of mixing valve

 System mounted on strut, galvanized. Strut shall be assembled with three hole flange angle plate on corners, four hole tee plates or two hole flat plate connectors on all other support pieces Factory pre-assembled and tested as a complete system

 All electrical connections to be completed by Electrical Contractor

 Taco 0013 standard pump included and installed

 Optional Taco smart pump, 0034E PLUS, see options page for more info